Example: Downloading without reinitialization
In the following example it is displayed how to download without reinitialization.
Table 3-4 Downloading without reinitialization
Step Instruction
1. Requirement: a memory reserve has to be set (see above)
2. Open, e.g. an optimized global DB.
3. Click the “Download without reinitialization” button and confirm the dialog with
“OK”
4. Add a new tag (retentive tags are also possible).
5. Download the block to the controller.
6. Result:
Actual values of the block remain
Note
Further information can be found in the online help of the TIA Portal under
“Loading block extensions without reinitialization”.
You will find further information in the following entry:
What options does the S7-1500 provide for downloading data in RUN?
http://support.automation.siemens.com/WW/view/en/76278126
3.2.8 Reusability of blocks
The block concept offers you a number of options to program in a structured and
effective way.
Advantages
Blocks can be used universally in any location of the user program.
Blocks can be used universally in different projects.