Data Sheet for Product
Siemens Industry, Inc. Page 7 of 8
Standard Object Types Supported
Product
Object Type
Creatable
Deletable
BACnet Energy
Meter Kits with CTs
Analog Value
No
No
Device
No
No
Data Link Layer Options
Product
Data Link and Options
BACnet Energy
Meter Kits with CTs
BACnet IP, (Annex J), Foreign Device (MD-BMED only)
MS/TP master (Clause 9), baud rate(s): 9600 bps, 19200 bps, 38400 bps, 76800 bps
Segmentation Capability
Product
Segmentation Type
Supported
Window Size
BACnet Energy
Meter Kits with CTs
Can transmit segmented messages
No
N/A
Can receive segmented messages
No
N/A
Device Address Binding
Product
Static Device Binding Supported
BACnet Energy
Meter Kits with CTs
No
Networking Options
Product
Network Options Supported
Supported
BACnet Energy
Meter Kits with CTs
Router, Clause 6
No
Annex H, BACnet Tunneling Router over IP
No
BACnet/IP Broadcast Management Device (BBMD)
Does the BMD support registrations by Foreign Devices?
No
Network Security Options
Product
Security Options Supported
BACnet Energy
Meter Kits with CTs
Non-secure Device – is capable of operating without BACnet Network Security.