Operating Instructions

Siemens Industry, inc. 44
Wiring the MD-xxHD Meter in a Single-Phase Application
The MD-xxHD meter is internally powered through the voltage between L1 and L2. For single-phase
installations where no L2 exists it is advised to jumper N to L2. This connection provides power to the
meter while maintaining Neutral as the metering voltage reference.
Current Transformer Basics
Ensure CTs meet the following criteria:
600 Vac UL Rated
UL2808 Listed
1/3 (333 mV) output voltage
Appropriate range for the circuit (5-120% of CT rating recommended)
Read the label.
Ensure CT orientation and placement:
Arrow points toward load (or as instructed by CT label).
Arrow points away from Panel (or as instructed by CT label).
Placed on First Conductor of voltage Reference (L1-L2) circuits are
placed on L1.
Observe wiring color and polarity.
Use the Shield wire if provided (connect to PCB terminal marked S).
Wiring Guide for CT Types
Split, Hinged, and Solid Core CTs
RōCoil CTs
White: Positive
Black: Negative
(no shield)
White: Positive
Brown: Negative
Bare Wire: Shield