Operating Instructions

41 Siemens Industry, Inc.
STEP 4. Reattach the TouchSāf™ high voltage cover.
STEP 5. Connect CT and Communications Wiring.
Connecting Voltage
Connect the voltage leads (L1, L2, L3, and N, as necessary) to the meter through a dedicated disconnect
or circuit breaker. A voltage lead of 14 AWG THHN Minimum 600VAC rating (or equivalent) is required.
IMPORTANT: Verify the circuit breaker is marked as the disconnect breaker for the meter.