Operating Instructions

39 Siemens Industry, Inc.
STEP 5. Attach high voltage cover.
STEP 6. Connect CT and Communications Wiring.
Connecting Voltage
Connect the voltage leads (L1, L2, L3, and N, as necessary) to the meter through a dedicated disconnect
or circuit breaker. A voltage lead of 14 AWG THHN Minimum 600VAC rating (or equivalent) is required.
IMPORTANT: Verify the circuit breaker is marked as the disconnect breaker for the meter.
IP30
TOUCH SAFE (with internal cover installed)