Data Sheet for Product
7/10
CA1N4454en Modulating control valves with magnetic actuator, PN16 CA1N4454en
Building Technologies 2017-11-30
Technical Data
Functional actuator data M3P80FY
M3P80FYP
M3P100FY
M3P100FYP
Power supply
Extra low-voltage only (SELV, PELV)
Operating voltage AC 24 V °20% (SELV) or
AC 24 V class 2 (US)
Frequency 50…60 Hz
Typical power consumption P
med
20 W 30 W
stand by (valve closed) < 2 W < 2 W
Rated apparent power S
NA
80 VA 120 VA
Minimal required transformer
power S
TR
100 VA 150 VA
Required fuse I
F
slow, see table «Connection type», page 4
External supply line protection Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to EN 60898
or
Power source with current limitation of max. 10 A
Input
Positioning signal Y DC 0…10 V or DC 4…20 mA
Impedance DC 0...10 V > 400 kς // 30 nF (load < 0.1 mA)
DC 4…20 mA 100…120 ς // 30 nF
Output Position feedback signal DC 0...10 V (max. 9.7 V ± 0.2 V)
Max. load
Stroke measurement
Nonlinearity
max. 1.5 mA
Inductive
± 3 % of end value
Positioning time < 2 s
Electrical wiring Cable entry 2 x Ø 13.1 mm
Connection terminals Screw terminals for max. 1 x 4 mm
2
wire
Minimal wire cross-section 1.5 mm
2
Maximum cable length refer to "Connection type", page 4
Functional valve data PN class PN 16 to EN 1333
Permissible operating pressure 1 MPa (10 bar)
Differential pressure Δp
max
/ Δp
s
refer to table "Type summary", page 2
Valve characteristic linear (to VDI / VDE 2173), optimized near the clos-
ing point
Leakage rate at Δp = 100 kPa
(1 bar)
1 ↑ 3 max. 0.05 % k
vs
2 ↑ 3 ca. 2 % k
vs
depending on operating condi-
tions