Data Sheet for Product
5/10
CA1N4454en Modulating control valves with magnetic actuator, PN16 CA1N4454en
Building Technologies 2017-11-30
Engineering notes
Conduct the electric connections in accordance with local regulations on electric
installations as well as the internal or connection diagrams.
Safety regulations and restrictions designed to ensure the safety of people and
property must be observed at all times!
A strainer should be fitted upstream of the valve. This increases reliability.
Mounting notes
Two mounting instruction leaflets are enclosed with the valve: Ref. 35638 (valve)
and reference 35731 (terminal housing).
The valve may only be used as a mixing or throughport valve, not as a diverting
valve. Observe the direction of flow 1 ⇓ 3!
90°
436 2Z 01
90°
It is essential to maintain the specified minimum clearance above and to the side of the
actuator and/or electronics module! (refer to "Dimensions", page 10)
Close off port '2' with the type Z155/... accessories,
which must be ordered separately. For details see
page 2.
The blank flange kit consists of a seal, screws,
spring washers and nuts.
4741Z01
Installation notes
∂ The actuator must not be lagged
∂ For notes on electrical installation, see "Connection terminals" respectively
"Connection diagram", page 9.
Attention
Attention
Attention
Orientation
Access for installation
Use as straight-
through valves