Data Sheet for Product
4/10
CA1N4454en Modulating control valves with magnetic actuator, PN16 CA1N4454en
Building Technologies 2017-11-30
When sizing valves for media other than water, note that the medium properties
∂ specific heat
∂ density
∂ kinematic viscosity
differ from water. All variables depend on temperature.
The design temperature is the lowest medium temperature in the valve.
Viscosity may change considerably on temperature changes depending on the medi-
um. Plant functionality may be impaired if the medium temperature does not guarantee
viscosity values compatible with troublefree valve functioning.
Kinematic viscosity τ [mm
2
/s] in HVAC plants always is lower than 10 mm
2
/s, i.e. its
influence on volume flow is negligible.
For details please contact your local Siemens branch office.
Linear
Volumetric fl
ow
Positioning signals
The 4-wire connection to the valve should always be given preference!
S
NA
P
MED
S
TR
I
F
Wire cross-section [mm
2
]
1
.
5
2
.
5
4
.
0
Typ
e refere
n
ce
[VA]
[W]
[VA]
[A]
max. cable length L
[m]
M3P80FY 80 20 100 6.3 10 16 27
M3P100FY 120 30 150 10 6 10 17
M3P80FYP 80 20 100 6.3 10 16 27
M3P100FYP 120 30 150 10 6 10 17
M3P80FY 80 20 100 6.3 10 16 27
M3P100FY 120 30 150 10 6 10 17
M3P80FYP 80 20 100 6.3 10 16 27
M3P100FYP 120 30 150 10 6 10 17
S
NA
= nominal apparent power for selecting the transformer
P
med
= typical power consumption
S
TR
= Minimal required transformer power
I
N
= required slow fuse
L = max. cable length; with 4-wire connections, the max. permissible length of the separate
1.5 mm
2
copper positioning signal wire is 200 m
1)
All information at AC 24 V
Note on viscosity
Kinematic viscosity
≤ 10 mm
2
/s
> 10 mm
2
/s
Valve characteristic
Connection type
1)
4-wire connection
3-wire connection