User Manual
5/10
Building Technologies Modulating Control Valve PN 16 with Magnetic Actuator CA2N4741en
HVAC Products 2018-02-14
Mounting Notes
Mounting Instructions are included in the packaging:
No: 35582 (valve)
No. 35541 (terminal housing ZM…)
The valve may only be used as a mixing or throughport valve, not as a diverting
valve. Observe the direction of flow!!
A strainer should be fitted upstream of the valve. This increases reliability.
Any
4 74 1Z 03
Only three-way valves are supplied. They may be
used as straight-through valves.
Port «2» can be sealed with Z155/... which must be
ordered as a separate item. The blank flange set
comes complete with blank flange, seal, screws,
spring washers and nuts.
DN15…DN32 blank flange (Z155/15F…Z155/32F)
DN40…DN50 blank flange (Z155/40…Z155/50)
4741Z01
Installation Notes
The actuator may not be lagged.
For notes on electrical installation, see «Connection terminals» resp. «Connection
diagrams»
Maintenance Notes
The valves and actuators are maintenance-free.
The low friction and robust design make regular servicing unnecessary and ensure a
long service life.
The valve stem is sealed from external influences by a maintenance-free gland.
Always disconnect power before fitting or removing the terminal housing.
Under operating conditions within the limits defined by the application data, the
actuator will become hot, but this does not represent a burn risk. Always
maintain the minimum clearance specified, refer to «Dimensions».
Vorsicht
Orientation
Use as straight-through
valves
Caution
Caution