Product Overview
3 / 6
Siemens Modulating pilot valve, PN 32 CA2N4731en
Building Technologies 09.06.2010
Engineering notes
The characteristics of the main valve and the manufacturer's recommendations
must be observed.
Mounting notes
Mounting instructions are enclosed with the valve:
•
Nr. 35552 (pilot valve)
The pilot valve can be mounted in any orientation, but upright mounting is preferable.
To protect the valve from dirt, a mesh filter should be fitted on the supply side (mesh
gauge 0.1...0.2 mm).
The pilot valve can be fitted directly to various commercially available main valves, with
the M24 x 1.5 screwed spigot.
Note, however, that it must not be screwed into the valve body until welding or solder-
ing work is complete.
To prevent damage to the O-ring and to protect the pilot valve from dirt and metal fill-
ings, the protective cap on the spigot should not be removed until immediately before
the valve is fitted.
Always switch off the power supply before connecting or disconnecting the ZM.. termi-
nal housing.
Maintenance notes
The M2FP03GX pilot valve is maintenance-free.
The pilot valve cannot be repaired. It has to be replaced as a complete unit.
Disposal
The device must not be disposed of together with domestic waste. This applies in
particular to the PCB.
Legislation may demand special handling of certain components, or it may be sen-
sible from an ecological point of view
Current local legislation must be observed.
Warranty
Application-specific technical data must be observed.
If specified limits are not observed, Siemens Switzerland Ltd / HVAC Prod-
ucts will nor assume any responsibility.
Caution
Attention
Attention
Repair