Data Sheet for Product

Table 1. RT APOGEE P oints, Application Number: 5856. (co nt inued)
Point Type Description Range/Units
abc
56 LDI
Compressor 2 Contactor Status Off/On
57
LDI
Compressor 2 Liquid Line Solenoid Status Off/On
58 LDI
Compressor 2 Unloader Solenoid Valve 1 Off/On
59 LDI
Compressor 2 Unloader Solenoid Valve 2 Off/On
60 LAI
Air Handling Unit Safety Shutdown Code
61 LAI
Compressor 1 Operating Code
62 LAI
Compressor 1 Fa ult Code
63 LAI
Compressor 2 Operating Code
64 LAI
Compressor 2 Fa ult Code
65 LAI
Total Number Of Condenser Fans Running
66 LAI
Cooling Load Steps Available
67 LAI
Actual Heating S et Point °F
°C
68 LAI
Actual Cooling Set Point °F
°C
69 LAI
Actual Discharge Air Temperature Set Point °F
°C
70 LAI
Actual Discharge Static Pressure Set Point IN WC
Pa
71 LAI
Actual Building Static Pressure Set Point IN WC
Pa
72 LAI
Low Ambient Cutout °F
°C
73 LAI
High Ambient Cutout °F
°C
74 LAI
Low Pressure Cutout
psig
kPa
75
LAI
High Pressure Cutout
psig
kPa
76 LAI
Discharge Air Temperature Cutout °F
°C
77
LDI
Hot Gas Option Selected Yes/No
78 LDI
Ambient Temperature Control Low/Stndrd
79 LDI Discharge Pressu re Transducer Insta lled
Yes/No
80
LDO Start/Stop Off/On
81
LDO Compressor 1 Remote Lead Manua l Select Auto/Lead
82
LDO Compressor 2 Remote Lead Manua l Select Auto/Lead
83
LAO Return Air Set Point °F
°C
continued on next page...
Siemens Building Technologies, Inc. Page 3 of 4
Document No. 127-1577