Data Sheet for Product
Table 1. RT APOGEE Points, Application Number: 5856. (continued)
Point Type Description Range/Units
abc
25 LAI Exhaust Fan Run Time hrs
26 LAI
Supply Fan Inlet Guide Van e Position %
27 LAI
Exhaust Fan Inlet Guide Vane Position %
28 LAI
Anti-Coinciden t Timer
–
29 LAI
Compressor 1 Run Time
hrs
30 LAI
Compressor 1 Oil P ressure
psig
kPa
31 LAI
Compressor 1 Suction Pressure
psig
kPa
32 LAI
Compressor 1 Discharge Pressure
psig
kPa
33 LAI
Compressor 1 Anti-Recycle Timer
–
34 LAI
Compressor 1 Number Of Stages Operating
–
35 LAI
Compressor 2 Run Time
hrs
36 LAI
Compressor 2 Oil P ressure
psig
kPa
37 LAI
Compressor 2 Suction Pressure
psig
kPa
38 LAI
Compressor 2 Discharge Pressure
psig
kPa
39 LAI
Compressor 2 Anti-Recycle Timer
–
40 LAI
Compressor 2 Number Of Stages Operating
–
41 LDI
Panel On/Off Switch Off/On
42 LDI Unit Run Permissive
Off/On
43 LDI Air Handling Unit Alarm
Normal/Alarm
44 LDI
Remote Status Remote/Local
45 LDI
Lead Compressor Off/On
46 LDI
Supply Fan Status Off/On
47 LDI
Return/Exhaust Fan Status Off/On
48 LDI
Current Ventilation Mode Ratemp/Oatemp
49 LDI
Compressor 1 Lockout Status Yes/No
50 LDI
Compressor 1 Contactor Status Off/On
51 LDI
Compressor 1 Liquid Line Solenoid
Status
Off/On
52 LDI
Compressor 1 Unloader Solenoid Valve 1 Off/On
53 LDI
Compressor 1 Unloader Solenoid Valve 2 Off/On
54 LDI
Compressor 1 Hot Gas Bypass Valve Status Off/On
55
LDI
Compressor 2 Lockout Status Yes/No
continued on next page...