Data Sheet for Product
Table 1. YG APOGEE Points, Application Number: 5864. (continued)
Point Type Description Range/Units
abc
24 LAI
Engine Manifold Pressure
psig
kPa
25 LAI
Leaving Chilled Water Temperature - Actual Setpoint °F
°C
26 LAI
Remote/ Local Actual Engine Load Set Point %
27 LAI
Evaporator Saturation Temperature °F
°C
28 LAI
Condenser Saturation Temperature °F
°C
29 LAI Discharge Te mperature
°F
°C
30 LAI
Oil Temperature °F
°C
31 LAI
Accumulated Operating Time
hrs
32 LAI
Accumulated System Starts
–
33 LAI
Low Oil Transducer Pressure
psig
kPa
34 LAI
High Oil Transducer Pressure
psig
kPa
35 LDI
Engine Panel Safety Shutdown Switch Status Off/On
36 LDI
Vent Valve Status Off/On
37 LDI
Chilled Water Pu mp Status Off/On
38 LDI
Start S witch Status Off/On
39 LDI
Chilled Water Flow Switch Status Off/On
40 LAI
Anti-Recycle Time Left
mins
41 LAI
Operating Mode
–
42 LAI
Operating Code
–
43 LAI
Safety Shutdown Code
–
44 LAI
Cycling Code
–
45 LAI Engine Type
–
46 LAI
Proximity Sensor - Actual Position
–
47 LAI
Proximity Sensor - Reference Positi
on
–
48 LAI Drain Line Th ermocouple Temperature
°F
°C
49 LAI
Delta P/P 3
–
50 LAI
Surface Speed3
–
continued on next page...
Page 2 of 4 Siemens Building Technologies, Inc.
Document No. 127-1585