Data Sheet for Product
Table 1. YP APOGEE Points, Application Number: 5859. (continued)
Point Type Description Range/Units
abc
22 LAI Entering Hot Water Temperature
°F
°C
23 LAI
Burner Command Or Percent Loading
–
24 LAI
Leaving Chilled Water Actual Set Point °F
°C
25 LAI
Leaving Hot Water Temperature A ctual Set Point °F
°C
26 LAI
Refrigerant Temperature °F
°C
27 LAI
Solution Temperature °F
°C
28 LAI Purge Pump Pressure psig
kPa
29 LAI Purge Tank Pressure psig
kPa
30 LAI
Accumulated Operating Time
hrs
31 LAI
Accumulated System Starts
–
32 LAI
Lifetime Purge Count
–
33 LDI
Refrigerant Pump Status Off/On
34 LDI
Condenser Pump Status Off/On
35 LDI
Chilled Water Pump Status Off/On
36 LDI
Start Switch Status Off/On
37 LDI
Hot Water Pump Status Off/On
38 LDI
Solution Pump 1 Status Off/On
39 LDI
Solution Pump 2 Status Off/On
40 LDI
Purge Pump Motor Status Off/On
41 LDI
Chilled Water Flow Switch Status Off/On
42 LDI
Hot Water F lo w Switch Stat us Off/On
43 LDI
Condenser Water Flow Switch Status Closed/Open
44 LDI
Dilution Cycle Active Yes/No
45 LAI
Operating Code
–
46 LAI
Operating Mod e
–
47 LAI
Warning Code
–
48 LAI
Safety Shutdown C ode
–
49 LAI
Cycling Code
–
50 LAI
Remote Lo ading Set Point
–
51 LAI Maximum Loading
–
52 LAI 7 Day Purge To tal
–
continued on nex t page...
Page 2 of 4 Siemens Building Technologies, Inc.
Document No. 127-1579