Data Sheet for Product

Table 1. YP APOGEE Points, Application Number: 5859. (continued)
Point Type Description Range/Units
abc
22 LAI Entering Hot Water Temperature
°F
°C
23 LAI
Burner Command Or Percent Loading
24 LAI
Leaving Chilled Water Actual Set Point °F
°C
25 LAI
Leaving Hot Water Temperature A ctual Set Point °F
°C
26 LAI
Refrigerant Temperature °F
°C
27 LAI
Solution Temperature °F
°C
28 LAI Purge Pump Pressure psig
kPa
29 LAI Purge Tank Pressure psig
kPa
30 LAI
Accumulated Operating Time
hrs
31 LAI
Accumulated System Starts
32 LAI
Lifetime Purge Count
33 LDI
Refrigerant Pump Status Off/On
34 LDI
Condenser Pump Status Off/On
35 LDI
Chilled Water Pump Status Off/On
36 LDI
Start Switch Status Off/On
37 LDI
Hot Water Pump Status Off/On
38 LDI
Solution Pump 1 Status Off/On
39 LDI
Solution Pump 2 Status Off/On
40 LDI
Purge Pump Motor Status Off/On
41 LDI
Chilled Water Flow Switch Status Off/On
42 LDI
Hot Water F lo w Switch Stat us Off/On
43 LDI
Condenser Water Flow Switch Status Closed/Open
44 LDI
Dilution Cycle Active Yes/No
45 LAI
Operating Code
46 LAI
Operating Mod e
47 LAI
Warning Code
48 LAI
Safety Shutdown C ode
49 LAI
Cycling Code
50 LAI
Remote Lo ading Set Point
51 LAI Maximum Loading
52 LAI 7 Day Purge To tal
continued on nex t page...
Page 2 of 4 Siemens Building Technologies, Inc.
Document No. 127-1579