Data Sheet for Product
Table 1. YS APOGEE Points, Application Number: 5860. (continued)
Point Type Description Range/Units
abc
25 LAI
Phase C -A Line Voltage
V
26 LAI
Leaving Chilled Water Temperature Actual Set Point °F
°C
27 LAI
Remote/Local Current Actual Set Point %
28 LAI
Evaporator Saturation Temperature °F
°C
29 LAI
Condenser S aturation Temperature °F
°C
30 LAI D ischarge Temperature
°F
°C
31 LAI
Oil Temperature °F
°C
32 LAI
Differential Filter Pressure
psid
kPa
33 LAI
Accumulated Operating Time
hrs
34 LAI
Accumulated System Starts
–
35 LAI
Minimum Current Limit Set Point3
A
36 LAI
Percent Slide Valve Position3 %
37 LDI
Compressor Motor Status Off/On
38 LDI
Oil Line Solenoid Status Off/On
39 LDI
Chilled Water Pump Status Off/On
40 LDI
Start Switch Status Off/On
41 LDI
Chilled Water Flow Switch Status Off/On
42 LDI
Eductor Sol en oid Status Off/On
43 LDI
Low Oil Separator Status Off/On
44 LDI
Ice Store Enable3 Off/On
45 LAI
Anti-Recycle Time Left
mins
46 LAI
Operating Mod e
–
47 LAI
Operating Code
–
48 LAI
Safety Shutdown C ode
–
49 LAI
Cycling Code
–
50 LAI
Leaving Water Restart Offset3
–
51
LDO Chiller Start/Stop Off/On
52
LAO Leaving Chilled Water Temperature Set Point °F
°C
53
LAO Load Limit Set Point %
a
Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
b
This column indicates the value/range or engineering units or both if known.
c
The default English value is not italicized. An italicized entry indicates an S I value.
Page 2 of 4 Siemens Building Technologies, Inc.
Document No. 127-1581