Data Sheet for Product

Table 1. C1 Mas ter APOGEE Points, Applicatio n Number: 5853. (continued)
Point Type Description Range/Units
abc
56 LAI
Lead Compressor Number
57
LAI
Leaving Chilled Water Temperature Actual Set Point °F
°C
58 LAI
Low Chilled Water Temperatu re Cutout °F
°C
59 LAI
Low Ambient Temperature Cutout °F
°C
60 LAI
High Ambient Temperature Cutout °F
°C
61 LAI
Low Suction Pressure Cuto ut
psig
kPa
62 LAI
High Discharge Pressure Cutout
psig
kPa
63 LAI
Remote Temperature Set Point °F
°C
64 LAI Remote Temperature Range
°F
°C
65 LAI
Local Cooler Barrel Set Point °F
°C
66 LAI
Compressor 1 Run Time
67 LAI
Compressor 2 Run Time
68 LDI Load Permissive
Off/On
69
LDO Chiller Start/Stop Off/On
70
LDO Load The Chiller Yes/No
71
LDO Unload The Chiller Yes/No
72
LAO Leaving Chilled Water Temperature Set Point °F
°C
73
LAO Remote Current Limit Set Point %
74
LAO Lead Unit Number Set Point
a
Values noted for LDIs and LDOs a re in the following format: O F F text/ON text.
b
This column indicates the value/range or engineering units or both if known.
c
The default English value is not italicized. An italicized entry indicates an S I value.
Siemens Building Technologies, Inc. Page 3 of 4
Document No. 127-1574