Data Sheet for Product

Table 1. Curbmaster YCU APOGEE Points, Application Number: 5863. (continued)
Point Type Description Range/Units
abc
25 LAI
Compressor 1 Starts
26 LAI
Compressor 1 Anti-Recycle Timer
27 LAI
Anti Coincidence Timer
28 LAI
Compressor 2 Oil Temperature °F
°C
29 LAI
Compressor 2 Oil Pressure
psig
kPa
30 LAI
Compressor 2 Suction Pressure
psig
kPa
31 LAI
Compressor 2 Discharge Pressure
psig
kPa
32 LAI
Compressor 2 Percent Fla %
33 LAI
Compressor 2 Total Run Time
hrs
34 LAI
Compressor 2 Starts
35 LAI
Load Steps Available
36 LDI
Chiller Run Status Off/On
37 LDI
Chiller Alarm Status Off/On
38 LDI
Condenser Water Pump Status Off/On
39 LDI
Compressor 1 Liquid Line Solenoid Valve Status Off/On
40 LDI
Compressor 1 Hot Gas Bypass Valve Status Off/On
41 LDI
Compressor 1 Reverse Condenser Fan Status Off/On
42 LDI
Compressor 2 Liquid Line Solenoid Valve Status Off/On
43 LDI
Compressor 2 Hot Gas Bypass Valve Status Off/On
44 LDI
Compressor 2 Reverse Condenser Fan Status Off/On
45 LAI
Compressor 1 Operating Code
46 LAI
Compressor 1 Fault Code
47 LAI
Compressor 2 Operating Code
48 LAI
Compressor 2 Fault Code
49 LAI
Compressor 1 Stages Operating
50 LAI
Compressor 1 Condenser Fan Forward
51 LAI
Compressor 2 Stages Operating
52 LAI
Compressor 2 Condenser Fan Forward
53 LAI
Lead Compressor
54 LAI
Discharge Air Temperature Actual Set Point °F
°C
55
LAI
Low Ambient Air Temperature Cutout Set Point °F
°C
continued on next page...
Page 2 of 4 Siemens Building Technologies, Inc.
Document No. 127-1584