Data Sheet for Product

Table 1. YK APO GEE Points, Application Num ber: 5858. (continued)
Point Type Description Range/Units
abc
24 LAI Phase A-B Line Voltage V
25 LAI
Phase B-C Line Voltage
V
26 LAI
Phase C-A Line Voltage
V
27 LAI
Leaving Chilled Water Temperature Actual Set Point °F
°C
28 LAI
Remote/Local Current Actual Set Point %
29 LAI
Evaporator Saturation Temperature °F
°C
30 LAI
Condenser S aturation Temperature °F
°C
31 LAI D ischarge Temperature
°F
°C
32 LAI
Oil Temperature °F
°C
33 LAI
Refrigerant Level3
psig
kPa
34 LAI
Accumulated Operating Time
hrs
35 LAI
Accumulated System Starts
36 LAI
Low Oil Transducer Pressure
psig
kPa
37 LAI
High Oil Transducer P ressure
psig
kPa
38 LDI
Compressor Motor Status Off/On
39 LDI
Vent Va lve Status 1 Off/On
40 LDI
Chilled Water Pump Status Off/On
41 LDI
Start Switch Status Off/On
42 LDI
Chilled Water Flow Switch Status3 Off/On
43 LDI
Adaptive Capacity Contro l Valid Surge Map3 Off/On
44 LDI
Adaptive Capacity Control Ne w Surge Po int3 Off/On
45 LDI
Vsd Cooling Pump Running3 Off/On
46 LDI Vsd Ieee 519 Filter Present3
No/Yes
47 LDI
Surge D etection Type3 Curent/Deltpp
48 LAI
Anti-Recycle Time Left
mins
49 LAI
Operating Mode
50 LAI
Operating Code
51 LAI
Safety Shutdown C ode
52 LAI
Cycling Code
continued on nex t page...
Page 2 of 4 Siemens Building Technologies, Inc.
Document No. 127-1580