Data Sheet for Product
Table 1. YI APOGEE Points, Application Number: 5857. (continued)
Point Type Description Range/Units
abc
55
LAI
Warning Message Code
–
56 LAI
Remote Load Set Point
–
57
LAI
Maximum Steam/Hot Water Valve Load Set Point
–
58 LAI
Weekly Purge Counter
–
59 LAI
Pulldown Demand Minutes Set Point
min
60 LAI
Pulldown Demand Minutes Left
min
61 LAI
Pulldown Demand Loading Start Set Point
–
62 LAI
Pulldown Demand Loading Stop Set Point
–
63 LAI Present Pul ldo wn Deman d Limit
–
64 LAI
Remote Temperature R ange Set Point °F
°C
65 LAI
Maximum Steam/Hot Water Val ve Unload Set Point
–
66 LAI
Maximum Entering Condenser Water Temperature Setpoint °F
°C
67 LAI
JP1 Status
–
68 LAI
JP3 Status
–
69 LAI
JPI Expansion Status
–
70 LDI
Refrigerant Level Solenoid Valve Status Off/On
71 LDI
Low Entering Condenser Water Temp erature Limit A ctive Yes/No
72 LDI Automatic Decrystallization Active
Yes/No
73 LDI Remote Load Limiting Active
Yes/No
74 LDI Pulldown Limiting Active
Yes/No
75
LDO Chiller Start/Stop Off/On
76
LAO Leaving Chilled Water Temperature Set Point ° F
°C
77
LAO Remote Current Limit Set Point %
a
Values noted for LDIs and LDO s are in the following format: OFF text/ON text.
b
This column indicates the value/range or engineering units or both if known.
c
The default English value is not italicized. An italicized entry indicates an SI value.
Siemens Building Technologies, Inc. Page 3 of 4
Document No. 127-1578