Data Sheet for Product

Table 1. YI APOGEE Points, Application Number: 5857. (continued )
Point Type Description Range/Units
abc
22 LAI
Local Leaving Chilled Water Set Point °F
°C
23 LAI
Purge P u m p Service Interval Set Point
hrs
24 LAI
Active Leaving Chilled Water Set Point °F
°C
25 LAI
Refrigerant Temperature °F
°C
26 LAI
Strong Solution Tempe rature °F
°C
27 LAI
Total Operating Time
hrs
28 LAI
Total System Starts
29 LAI
Lifetime Purge Count
30 LDI
Refrigerant Pump Status Off/On
31 LDI
Condenser Water Pump Status Off/On
32 LDI
Chilled Water Pump Status Off/On
33 LDI
Unit Switch Status Stop/Run
34 LDI
Pump Motor Coolant Solenoid Valve Status Closed/Open
35 LDI
Solution/Absorber Pump Motor Status Off/On
36 LDI
Generator Pump Motor Status Off/On
37 LDI
Purge Pump Motor Status Off/On
38 LDI
Chilled Water Flow Switch Status Closed/Open
39 LDI
Stabilizer Solenoid Valve Status Off/On
40 LDI
Condenser Water Flow Switch Status Closed/Open
41 LDI
Dilution Cycle Status Off/On
42 LDI
Refrigerant Level Flow Switch Status Closed/Open
43 LDI
Restart Control Manual/Auto
44 LDI
Load Overload No/Yes
45 LDI
English Units of Meas ure Si/Eng
46 LDI
Condenser Water Pump Limit No/Yes
47 LDI
Diagnostic Status DISABL_ENABLE
48 LDI
RTC Status Enable/Disabl
49 LDI
EXP German German/Englsh
50 LAI
Dilution Cycle Code
51 LAI
Operating Mode
52 LAI
Operating Code
53 LAI
Safety Shutdown C ode
54 LAI
Cycling Code
continued on next page...