Data Sheet for Product
2
127-1682
Smart Infrastructure
2020-20-07
Siemens FireFinder XLS Driver on the PXC Series Platform
Functionality
Figure 2: Typical Siemens FireFinder XLS and APOGEE Automation System Configuration (Firmware
Revision 3.x).
Notes on System Architecture
The Siemens FireFinder XLS Driver with Firmware Revision 3.
x
supports the following:
● BACnet/IP ALN on Firmware 3.
x
.
Do not use an Integration Driver as the router.
● Monitoring for a maximum of 64 FireFinder XLS panels (PMIs).
● TX-I/O Modules.
● Maximum of 8,000 APOGEE points per driver.
● A maximum of 64 FireFinder XLS panels FireFinder XLS nodes (PMIs) per driver.