Data Sheet for Product

Page 4 of 6 Siemens Building Technologies, Inc.
Document No. 127-0020
Table 3. Warnings Mode (Point 13).
Value Mode
0 No Loop Flow Requested
1 Room Too Warm
2 Room Too Cool
4 Change Filter
8 Rapid Cycling
16 Bad DAT Sensor
32 Bad LWT Sensor
64 Unused
128 Request Loop Flow
Table 4. Faults (Points 14 and 15).
Value Mode
204 Room Temperature Sensor Fail
205 Low Discharge Air Temperature
206 Low Refrigerant Pressure
207 High Refrigerant Pressure
255 None
Table 5. Auto/Manual Mode (Point 27).
Value Mode
0 Manual Unoccupied
1 Manual Occupied
5 Manual Fan Only
9 Manual Off
255 Auto