Data Sheet for Product

Siemens Building Technologies, Inc. Page 3 of 6
Document No. 127-0020
Table 2. Operating Mode (Point 06).
Value Mode
0 Unoccupied
1 Occupied
2 Override
3 Occupied – Load Shed. Allows the Water Source
Heat Pump to distribute the heating/cooling Set Points
based on the load shed level set at the WSHP
controller.
4 Occupied – Load Shed. Allows the Water Source
Heat Pump to distribute the heating/cooling Set Points
based on the load shed level set at the WSHP
controller.
5 Fan Only
8 Compressor Off
9 Unit Shutdown
190 Off – Condensate Overflow
191 Off – Brownout
204 Off – Room Temperature Sensor Fail
205 Off – Low Discharge Air Temperature
206 Off – Low Refrigerant Pressure
207 Off – High Refrigerant Pressure