Data Sheet for Product

Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 6
Document No. 127-0020
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Microtech 2000 Water Source Heat Pump
Table 1. Microtech 2000 Water Source Heat Pump.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5018
03 LAI Space Temperature °F
04 LAI Discharge Air Temperature °F
05 LAI Leaving Water Temperature °F
06 LAI Operating Mode See Table 2
07 LAI Fan Run Hours Hours
08 LAI Compressor Run Hours Hours
09 LAI Compressor Starts Starts
10 LAI Set Point Adjustment °F
11 LAI Heating Set Point °F
12 LAI Cooling Set Point °F
13 LAI Warnings See Table 3
14 LAI Current Fault See Table 4
15 LAI Previous Fault See Table 4
16 LDI Fan Status Off/On
17 LDI Compressor Status Off/On
18 LAO Unoccupied Cooling Room Set Point. Water Source Heat Pump
attempts to maintain room temperature by discharging a constant
temperature of air. For cooling, typical discharge temperature is
room temperature minus 20°F. Unit begins cooling based on room
temperature. If unit is in unoccupied time period, Set Point attempts
to maintain room temperature between unoccupied Set Points. If
room Set Point Adjustment is active, Set Points are adjusted based
on value of Set Point Adjustment (Point 10).
0 – 255°F
continued on next page...