Data Sheet for Product
Page 4 of 6 Siemens Building Technologies, Inc.
Document No. 127-0004
Table 2. Unit Status (Point 03).
Value Description
1 Off – Manual Mode
2 No Communication to Units
3 Off – Remote Communication
4 Off – Remote Switch
5 All Units Off
6 Off – Time Clock
7 Off – Ambient Lockout
9 Chiller 1 Enabled
10 Chiller 2 Enabled
11 Chillers 1 and 2 Enabled
12 Chiller 3 Enabled
13 Chillers 1 and 3 Enabled
14 Chillers 2 and 3 Enabled
15 All Units Enabled
16 Manual Sequencing
Table 3. Sequence Order (Points 04 and 65).
Value Description
0 No.1 – No.2 – No.3
1 No.1 – No.3 – No.2
2 No.2 – No.1 – No.3
3 No.2 – No.3 – No.1
4 No.3 – No.1 – No.2
5 No.3 – No.2 – No.1