Data Sheet for Product
Siemens Building Technologies, Inc. Page 3 of 6
Document No. 127-0004
Table 1. Remote Monitoring/Sequencing (RMS) Panel for Reciprocating and Screw Chillers.
Point Type Description Range/Units
59 LAI Cooling Degree Days November Degree Days
60 LAI Cooling Degree Days December Degree Days
61 LAI Cooling Degree Days Total This Year Degree Days
62 LAI Cooling Degree Days Total Last Year Degree Days
63 LAO Control Mode 0 = All Off
1 = Automatic
2 = Manual Sequencing
64 LAO Number of Chillers On in Active Sequence 0 = None
1 = First
2 = First and Second
3 = All
65 LAO Chiller Sequence Order See Table 3
66 LAO Lag On at Stage See Table 4
67 LAO Lag Off at Stage See Table 4
68 LAO Delay Lag Timer 1 – 9 Minutes
69 LDO Standby No/Yes
70 LAO Resequence Day 1=Sunday, 7=Saturday
71 LAO Resequence Hour 0 – 23 Hours
72 LAO Resequence Minute 0 – 59 Minutes
73 LAO Leaving Evaporator Reset Signal 0 – 20 mA
74 LAO Leaving Evaporator Reset Option 0 = None
1 = 4 – 20 mA
2 = Outside Air Temperature
75 LAO Outside Air Temperature Begin Reset
0 – 90°F
76 LAO Outside Air Temperature Max Reset
0 – 90°F
77 LAO Demand Limit Signal 0 – 20 mA
78 LDO Ambient Lockout Option No/Yes
79 LAO Ambient Lockout Set Point
0 – 95°F
99 LDI Device Communication Failure Normal/Failed