Data Sheet for Product
Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 6
Document No. 127-0004
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Remote Monitoring/Sequencing (RMS) Panel for
Reciprocating and Screw Chillers
Table 1. Remote Monitoring/Sequencing (RMS) Panel for Reciprocating and Screw Chillers.
Point Type Description Range/Units
01 LAO Device Address —
02 LAO Application Number 5058
03 LAI Unit Status See Table 2
04 LAI Sequence Order See Table 3
05 LAI Outdoor Air Temperature
-40 – 150°F
06 LAI Zone Temperature
-40 – 150°F
07 LAI Chiller No.1 January Run Hours Hours
08 LAI Chiller No.1 February Run Hours Hours
09 LAI Chiller No.1 March Run Hours Hours
10 LAI Chiller No.1 April Run Hours Hours
11 LAI Chiller No.1 May Run Hours Hours
12 LAI Chiller No.1 June Run Hours Hours
13 LAI Chiller No.1 July Run Hours Hours
14 LAI Chiller No.1 August Run Hours Hours
15 LAI Chiller No.1 September Run Hours Hours
16 LAI Chiller No.1 October Run Hours Hours
17 LAI Chiller No.1 November Run Hours Hours
18 LAI Chiller No.1 December Run Hours Hours
19 LAI Chiller No.1 Total This Year Hours
20 LAI Chiller No.1 Total Last Year Hours
21 LAI Chiller No.2 January Run Hours Hours
22 LAI Chiller No.2 February Run Hours Hours
23 LAI Chiller No.2 March Run Hours Hours
24 LAI Chiller No.2 April Run Hours Hours
continued on next page...