Table 1. Remote Monitoring and Control Panel for Rooftop Units.
Point Type Description Range/Units
42 LAO Group 3 Pressure Calculation 0 = Minimum Static Pressure
1 = Maximum Static Pressure
2 = Average
43 LAO Group 3 Pressure Set Point 0 – 4 IWC
44 LDO Group 4 Control Temperature Choice. Control temperature set point
indicates which temperature value to use as control temperature.
(Point 7)
Return Temperature/
Space Temperature
45 LAO Group 4 Temperature Calculation 0 = Minimum Temperature
1 = Maximum Temperature
2 = Average
46 LAO Group 4 Pressure Calculation 0 = Minimum Static Pressure
1 = Maximum Static Pressure
2 = Average
47 LAO Group 4 Pressure Set Point 0 – 4 IWC
48 LAO Group Number For Unit 6. Rooftop units can be combined into
groups for common control.
0 = Not Associated With Group
1 – 4 = Unit Number
99 LDI Device Communication Failure Normal/Alarm