Table 1. RMC Monitoring and Control Panel for Self-Contained Air Conditioning Units.
Point Type Description Range/Units
48 LAO Group No. 4 Control Temperature Choice 0 = Return Air
1 = Space
49 LAO Group No. 4 Temperature Calculation 0 = Based on Minimum
1 = Based on Maximum
2 = Based on Average
50 LAO Group No. 4 Pressure Calculation 0 = Based on Minimum
1 = Based on Maximum
2 = Based on Average
51 LAO Group No. 4 Pressure Set Point 0 – 4 IWC
99 LDI Device Communication Failure Normal/Failed