Data Sheet for Product

Page 2 of 4 Siemens Building Technologies, Inc.
Document No. 127-0013
Table 1. RMC Monitoring and Control Panel for Self-Contained Air Conditioning Units.
Point Type Description Range/Units
23 LAO Unit No. 4 Address. (See Note for Point 20) 1 – 254
24 LAO Unit No. 5 Address. (See Note for Point 20) 1 – 254
25 LAO Unit No. 6 Address. (See Note for Point 20) 1 – 254
26 LAO Unit No. 7 Address. (See Note for Point 20) 1 – 254
27 LAO Unit No. 8 Address. (See Note for Point 20) 1 – 254
28 LAO Unit 1 Group Number 0 – 4
29 LAO Unit 2 Group Number 0 – 4
30 LAO Unit 3 Group Number 0 – 4
31 LAO Unit 4 Group Number 0 – 4
32 LAO Unit 5 Group Number 0 – 4
33 LAO Unit 6 Group Number 0 – 4
34 LAO Unit 7 Group Number 0 – 4
35 LAO Unit 8 Group Number 0 – 4
36 LAO Group No. 1 Control Temperature Choice 0 = Return Air
1 = Space
37 LAO Group No. 1 Temperature Calculation 0 = Based on Minimum
1 = Based on Maximum
2 = Based on Average
38 LAO Group No. 1 Pressure Calculation 0 = Based on Minimum
1 = Based on Maximum
2 = Based on Average
39 LAO Group No. 1 Pressure Set Point 0 – 4 IWC
40 LAO Group No. 2 Control Temperature Choice 0 = Return Air
1 = Space
41 LAO Group No. 2 Temperature Calculation 0 = Based on Minimum
1 = Based on Maximum
2 = Based on Average
42 LAO Group No. 2 Pressure Calculation 0 = Based on Minimum
1 = Based on Maximum
2 = Based on Average
43 LAO Group No. 2 Pressure Set Point 0 – 4 IWC
44 LAO Group No. 3 Control Temperature Choice 0 = Return Air
1 = Space
45 LAO Group No. 3 Temperature Calculation 0 = Based on Minimum
1 = Based on Maximum
2 = Based on Average
46 LAO Group No. 3 Pressure Calculation 0 = Based on Minimum
1 = Based on Maximum
2 = Based on Average
47 LAO Group No. 3 Pressure Set Point 0 – 4 IWC
continued on next page...