Data Sheet for Product
Page 2 of 4 Siemens Building Technologies, Inc.
Document No. 127-0555
Table 1. Direct Fired, Heating and Cooling (DC-S) Absorption Chiller.
Point Type Description Range/Units
35 – 36 LAI Absorbent Pump 1 Operating Hours —
37 – 38 LAI Burner Operating Hours —
39 – 40 LAI Refrigerant Pump Operating Hours —
41 LDI Operation Indication Off/On
42 LDI Answer Back Signal Off/On
43 LDI Alarm Indication Off/On
44 LDI Absorbent Pump 1 or Inverter (Alarm) Disable/Enable
45 LDI Absorbent Pump 1 Disable/Enable
46 LDI Absorbent Pump 2 (Alarm) Disable/Enable
47 LDI Absorbent Pump 2 Disable/Enable
48 LDI Auto Restart After Power Failure Disable/Enable
49 LDI Burner Signal Off/On
50 LDI Flame Failure Normal/Alarm
51 LDI Fuel Input Valve/Cooling Main Mode (Close) Off/On
52 LDI Fuel Input Valve/Cooling Main Mode (Open) Off/On
53 LDI Fuel Input Valve/Heating Main Mode (Close) Off/On
54 LDI Fuel Input Valve/Heating Main Mode (Open) Off/On
55 LDI Chilled Water Flow Rate No Flow/Flow
56 LDI Chilled And/Or Hot Water Pump Signal Off/On
57 LDI Chilled Water Pump Interlock Open/Closed
58 LDI Control Valve 1 Auto/Manual
63 LDI Control Valve 2 Auto/Manual
64 LDI Heating Main/Cooling Main Heating/Cooling
65 LDI Cooling Mode Off/On
66 LDI Cooling Water Flow Rate No Flow/Flow
67 LDI Cooling Water Pump Signal Off/On
68 LDI Cooling Water Pump Interlock Open/Closed
69 LDI Heating Mode Off/On
70 LDI High Temperature Generator Low Solution Level Normal/Alarm
71 LDI High Temperature Generator Pressure Normal/Alarm
73 LDI Hot Water Pump Interlock Open/Closed
74 LDI Purge Pump Off/On
75 LDI Refrigerant Pump (Alarm) Normal/Alarm
76 LDI Refrigerant Pump Off/On
continued on next page...