Data Sheet for Product
Siemens Building Technologies, Inc. Page 5 of 6
Document No. 127-0009
Table 3. Circuit Status (Points 04 through 07).
Value Description
0 Off – S-1 System Switch
1 Off – Manual Set Point
2 Off – Alarm
3 Off – Pump-down Switch
5 Off – Wait for Flood
7 Start Pump-down
8 Pump-down
9 Start Requested
10 Pre-purge
11 Open Solenoid
12 Low Ambient Start
13 Cooling
Table 4. Alarms (Points 46 through 49).
Value Description
0 No Alarm
1 High Condenser Pre-alarm Hold Stage
2 High Condenser Pre-alarm Stage-down
3 Freeze Refrigerant Pre-alarm Stage-down
4 Loss of Chilled Water Flow
5 No Pump-down
6 Low Evaporator No Start
7 Pre-purge Fail
9 Low Ambient Start
12 Refrigerant Freeze Protect
13 Low Evaporator Pressure
14 Motor Protect
15 Re-Power After Power Loss
17 No Condenser Water Flow
18 No Evaporator Pressure Drop
19 Low Lift Pressure
20 No Liquid Run
22 Low Oil Pressure
25 High Condenser Pressure
continued on next page...