Data Sheet for Product

Table 5. Reset Option (Point 51). (continued)
3
Network Chilled Water
Reset. Resets Chilled Water
Set Point based on the
Network Evaporator Leaving
Temperature Re s et. A sign al of
0 100% results in a linear reset
between the Chilled Water Set
Point and th e Maximum Chilled
Water Reset Set Point plus the
Chilled Water Set P oint.
4
Ice Chilled Water Reset. Resets
the Chilled Water S et Point
(typically 2 3°F) based upon a 4
–20mAsignal. Asignalless
than 4 mA results in no reset of
Chilled Water Temperature Set
Point. A signal greater than 4
mA results in a Chilled Water
Set Point equal to the set point
plus the Maximum Chilled Water
Reset Set Point (typically 22°F).
5
Outdoor Air Temperature Chilled
Water Reset.
Siemens Building Technologies, Inc. Page 7 of 8
Document No. 127-0011