Data Sheet for Product
Table 1. Two -Compressor Screw Chiller. (continued)
27 LAI
Compressor 1 Operating
Hours
0 – 65,279
28 LAI
Compressor 2 Operating
Hours
0 – 65,279
29 LAI
Compressor 1 Starts
0 – 65,279
30 LAI
Compressor 2 Starts
0 – 65,279
31 LAI
Circuit 1 Alarm See Table 4
32 LAI
Circuit 2 Alarm See Table 4
33 LAI
Circuit No. 1 Condition at
Time of Alarm: Capa city
0 – 100%
34 LAI
Circuit No. 1 Condition at
Time o f Alarm: Condenser
Leaving Water Temperature
or Outside Air Te mperature
-40–263°F
35 LAI
Circuit No. 1 Condition at
Time o f Alarm: Condenser
Pressure
0 – 450 psi
36 LAI
Circuit No. 1 Condition at
Time of Alarm: Evaporator
Leaving Water Temperature
-40–263°F
37 LAI
Circuit No. 1 Condition at
Time of Alarm: Fan Stage
0–6
38 LAI
Circuit No. 1 Condition at
Time of Alarm: Evaporator
Pressure
0 – 150 psi
39 LAI
Circuit No. 1 Condition at
Time of Alarm: Liquid Line
Temperature
-40–263°F
40 LAI
Circuit No. 1 Condition
at Time of Alarm: Suction
Temperature
-40–263°F
41 LAI
Circuit No. 2 Condition at
Time of Alarm: Capa city
0 – 100%
42 LAI
Circuit No. 2 Condition at
Time o f Alarm: Condenser
Leaving Water Temperature
or Outside Air Te mperature
-40–263°F
43 LAI
Circuit No. 2 Condition at
Time o f Alarm: Condenser
Pressure
0 – 450 psi
44 LAI
Circuit No. 2 Condition at
Time of Alarm: Evaporator
Leaving Water Temperature
-40–263°F
45 LAI
Circuit No. 2 Condition at
Time of Alarm: Fan Stage
0–6
continued on next page...
Siemens Building Technologies, Inc. Page 3 of 8
Document No. 127-0011