Table 3. Faults (Points 17 through 20).
Value Description
204 Room Temperature Sensor Fail
187 Low Discharge Air Temperature
188 Low Refrigerant Pressure
189 High Refrigerant Pressure
255 None
Table 4. Auto/Manual Mode (Point 36).
Value Description
1 Manual Occupied
5 Manual Fan Only
9 Manual Off
255 Auto
Table 5. System Command (Point 37).
Value Description
0 Not Received
8 On – Enable
9 On – Load Shed 1
10 On – Load Shed 2
11 On – Load Shed 3
12 On – Load Shed 4
13 On – Load Shed 5
14 On – Load Shed 6
15 On – Load Shed 7
24 Lockout Heat
32 Lock Out Cool
40 Lock Out Compressor
48 Unit Shutdown
64 Supplemental Heat Enabled
128 Clear Fault