Data Sheet for Product
Point Map
Rev. 1, February, 2002
Siemens Building Technologies, Inc. Page 1 of 8
Document No. 127-0550
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Constant Volume, Outside Air, Zone Control
Rooftop Unit
Table 1. Constant Volume, Outside Air, Zone Control Rooftop Unit.
Point Type Description Range/Units
01 LAO Device Address —
02 LAO Application Number 5016
03 LAI Supply Air Temperature
1 – 255°F
05 LAI Outdoor Air Temperature
-40 – 150°F
06 LAI Space Temperature
1 – 240°F
08 LAI Misc. Temperature 1 (Optional)
1 – 240°F
09 LAI Misc. Temperature 2 (Optional)
1 – 240°F
10 LAI Final Filter Pressure Drop (Optional) 0 – 4 IWC
11 LAI Filter Pressure Drop 0 – 4 IWC
15 LAI Humidity 0 – 100% rh
17 LAI Control Temperature See Table 2
18 LAI Unit Status See Table 3
19 LAI Stages of Cooling/Heating. Zero indicates no Heating or Cooling. —
21 LAI Cooling Control Status See Table 4
22 LAI Heating Control Status See Table 5
23 LAI Time Mode Status Occupied/Unoccupied
25 LDI Airflow Status No Airflow/Airflow
26 LDI Supply Fan Status Off/On
28 LAI Reheat Operating Hours Hours
29 LAI Dewpoint Temperature
°F
30 LAI Current Alarm (Buffer) See Table 6
31 LAI Cooling Stages Number
32 LAI Heating Stages Number
continued on next page…