Data Sheet for Product

Page 2 of 8 Siemens Building Technologies, Inc.
Document No. 127-0007
Table 1. Series 200 Flooded Screw Chiller.
Point Type Description Range/Units
25 LAI Condenser Water Temperature – Delta 0 – 263°F
26 LAI Condenser Water Temperature – Entering -40 – 263°F
63,985 = Short
27 LAI Condenser Water Temperature – Leaving -40 – 263°F
28 LDI Cooling Tower Control External/Chiller
29 LAI Cooling Tower Stage 0 – 6 Stages
30 LAI Cooling Tower Valve Position 0 – 100%
31 LAI Discharge Refrigerant Temperature -40 – 263°F
32 LAI Evaporator Approach Temperature 0 – 263°F
33 LAI Evaporator Pump Status See Table 3
34 LAI Evaporator Pump No. 1 Operating Hours 0 – 49,999
35 LAI Evaporator Pump No. 2 Operating Hours 0 – 49,999
36 LAI Evaporator Refrigerant Pressure 0 – 150 psig
37 LAI Evaporator Refrigerant Temperature -40 – 263°F
38 LAI Evaporator Water Flow Rate 0 – 6,553 GPM
39 LDI Evaporator Water Flow Status No Flow/Flow
40 LDI Evaporator Water Rate Sensor Not Present/Present
41 LAI Evaporator Water Temperature – Delta 0 – 263°F
42 LAI Evaporator Water Temperature – Entering -40 – 263°F
43 LAI Evaporator Water Temperature – Leaving -40 – 263°F
44 LAI Fault – Current Active See Table 4
45 LAI Liquid Line Refrigerant Temperature -40 – 263°F
46 LAI Liquid Line Pressure 0 – 450 psig
47 LAI Evaporator Temperature -40 – 263°F
48 LAI Condenser Evaporator Ratio 0 – 255
49 LAI Outdoor Air Temperature Method 0 = Not Present
1 = Local
2 = Network
50 LAI Outdoor Air Temperature – Local -40 – 152°F
51 LDI Refrigerant Detection Sensor Not Present/Present
52 LAI Refrigerant Leak Detection Limit 0 – 100 PPM
53 LAI Unit Status See Table 5
54 LAO Capacity Limit Percent 0 – 100%
55 LDO Clear Current Fault No Action/Clear Fault
56 LAO Chiller Operation Mode See Table 6
continued on next page…