Data Sheet for Product

Page 4 of 8 Siemens Building Technologies, Inc.
Document No. 127-0027
Table 2. Unit Status (Points 03, 65 and 66).
Value Description
0 Off – All Systems
1 Off – Alarm
2 Off – Ambient Temperature Lockout
3 Off – Panel Rocker Switch
4 Off – Manual
5 Off – Remote Switch
6 Off – Remote Communication
7 Off – Time Schedule
8 Start Requested
9 Waiting for Low Oil Sump Temperature
10 Evaporator Pump Off
11 Evaporator Pump On – Recirculation
12 Evaporator Pump On – Cycle Timer
13 Evaporator Pump On – Waiting for Load
14 Oil Pump Off
15 Oil Pump On – Pre-lubrication
16 Condenser Pump Off
17 Condenser Pump On – Waiting for Flow
18 Compressor Motor – Startup Unloading
19 Compressor Motor – Started
20 Compressor Motor – Running OK
21 Compressor Motor – Rapid Shutdown
22 Compressor Motor – Shutdown Unloading
23 Compressor Motor – Off Normal Shutdown
24 Condenser Pump – Off/Shutdown
25 Evaporator Pump – Off/Shutdown
26 Condenser Post Lubrication
27 Oil Pump – Off/Shutdown