Data Sheet for Product
Siemens Building Technologies, Inc. Page 3 of 8
Document No. 127-0027
Table 1. Series 200 Centrifugal Chiller.
Point Type Description Range/Units
60 LAO Motor Current Limit 0 – 100%
61 LAO Clear Current Fault —
62 LAO Watchdog Timer —
63 LAI Lead/Lag Status See Table 7
64 LAI Lead Unit Master/Slave
65 LAI Lead Unit Status See Table 2
66 LAI Lag Unit Status See Table 2
67 LAI Lead Motor Current 0 – 100% FLA
68 LAI Lag Motor Current 0 – 100% FLA
69 LDI Lead Unit Enabled —
70 LDI Lag Unit Enabled —
71 LAO Master/Slave Set Point Master/Slave
72 LAO Lead/Lag Set Point See Table 8
73 LAO Enable Lag Set Point 0 – 100%
74 LAO Disable Lag Set Point 0 – 100%
75 LDO Lag As Standby —
76 LAO Lead/Lag Switch Set Point (Day) See Table 9
77 LAO Lead/Lag Switch Set Point (Hour) 0 – 23
78 LDI Watchdog Status Timeout/OK
99 LDI Communication Status Normal/Failed