Data Sheet for Product

Point Map
Rev. 1, February, 2002
Siemens Building Technologies, Inc. Page 1 of 8
Document No. 127-0551
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Constant Volume, Outside Air, SAT Control
Rooftop Unit
Table 1. Constant Volume, Outside Air, SAT Control Rooftop Unit.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5017
03 LAI Supply Air Temperature
1 – 255°F
05 LAI Outdoor Air Temperature
-40 – 150°F
06 LAI Space Temperature
1 – 240°F
08 LAI Misc. Temperature 1 (Optional)
1 – 240°F
09 LAI Misc. Temperature 2 (Optional)
1 – 240°F
10 LAI Final Filter Pressure Drop (Optional) 0 – 4 IWC
11 LAI Filter Pressure Drop 0 – 4 IWC
17 LAI Control Temperature See Table 2
18 LAI Unit Status See Table 3
19 LAI Stages of Cooling/Heating. Zero Indicates No Heating or Cooling.
21 LAI Cooling Control Status See Table 4
22 LAI Heating Control Status See Table 5
23 LAI Time Mode Status Occupied/Unoccupied
25 LDI Airflow Status No Airflow/Airflow
26 LDI Supply Fan Status Off/On
30 LAI Current Alarm (Buffer) See Table 6
37 LDO Outside Air Source Type Local/Remote
45 LDO Clear Alarm. Warning and problem conditions are normally self-
clearing once abnormal condition is resolved. Fault conditions cause
unit to shut down and must be manually cleared. Refer to alarms
later in this section for more information.
Point Automatically Reset to 0 after
Alarm is cleared/Clears Active Fault.
46 LAO Control Mode See Table 7
continued on next page...