Data Sheet for Product

Table 1. LP-2500 and LP-3500— L P26 S eries and RCS Series 60 Zone Lighting Pane l AP OGEE Points, Applicatio n
Number: 5103.
(continued)
Point Type
a
Description Range/Value
b
59
LDO Zone 57 Status On/Off
N, *F*
60
LDO Zone 58 Status On/Off
N, *F*
61
LDO Zone 59 Status On/Off
N, *F*
62
LDO Zone 60 Status On/Off
N, *F*
63
LDO All Zones Off On/Off
64
LDO All Zones On On/Off
65 LDI Zone A larm
On/Off
66
LDO Unfail All Zones UNFAIL/NORMAL
c
67 LDI
Lumisys Panel Override Active On/Off
98 LAI Lumisys Panel Type
SeeTable2
99 LDI
Communication Failure On/Off
a
For all LAI and LAO points, use a Slope of 1.0 and an Intercept of 0.0 with a sensor type of I (current).
b
N = OK, *F* = One or more re lays in zone are out of synchronization
c
The value is shown in the subpoint log. An unbundled point will display ON/OF F only, where ON = Unfail points; OFF = Normal operation.
Table 2. Lumisys Panel Type (Point 98).
Lumisys Pane l Type 0 = Unkn own
1 = LP-2500
2 = LP-2600
3 = LP-2800
4 = RCS-1000
5=LP-3500