Installation Instructions

Document No. 565-717
Installation Instructions
April 30, 2009
Connecting the Barber-Colman
Network 8000 Enhanced Driver to
the Barber-Colman System
Follow these steps to connect the Barber-Colman
Network 8000 Enhanced Driver to the Barber-Colman
devices:
1. Make cab les per diagram in Figure 1.
2. Connect cables per diagram in Figure 1.
LCM block functionality and LCM bus
integration are not supported with the
Barber-Colman Network 8000 Enhanced
Driver.
FLN
DRIVER
+
-
S
-
+
BARBER-COLMAN
DEVICES
MicroZone II (MZ II)
MicroFlo II (MF II)
Package Equipment Module (PEM)
MicroNet Integrator (ASDI)
TAPE BACK
SHIELD
GW1341R1
RS-485 TRUNK CABLE
(MAX 4000’/1200 m;
STANDARD 24 AWG LOW CAPACITANCE)
ASD Bus
Figure 1. Connecting the Barber-Colman Network 8000 Enhanced Driver to the Barber-Colman System.