Data Sheet for Product
Table 1. Micro Net VAV Poin t Map, Application Number: 5715. (continu ed)
Point Type Description Range/Units
abc
25 LDI
DO1 Status Off/On
26 LDI
DO2 Status Off/On
27 LDI
DO3 Status Off/On
28 LAI Zone Temp
°F
°C
29 LAI Box Flow
–
30 LAI
Cool Output %
31 LAI
Heat Output %
32 LAI Aux Temp
°F
°C
33 LAI
Control Cool Setpoint °F
°C
34 LAI
Control Heat Setpoint °F
°C
35 LAI
Unocc Heat Setpoint °F
°C
36 LAI
Control Max Flow/Pos
–
37 LAI
Control Min Flow/Pos
–
38 LAI Reheat Minimum Flow
–
39 LAI Unocc Minimum Flow
–
40 LAI
Flow/Pos Setpoint
–
41 LAI
Velocity Pressure (IN WC) IN WC
Pa
42 LAI
Override Time (Min)
mins
43 LAI
Control Status
–
44 LAI
System Fa ult
–
45 LAI Application Error
–
a
Values noted for LDIs and LDOs are in the following format: O F F text/ON text.
b
This column indicates the value/range or engineering units or both if known.
c
The default English value is not italicized. An italicize d entry indicates an SI value.