Data Sheet for Product
Page 2 of 3
Siemens Building Technologies, Inc.
The Controller Board is a Neuron-based platform that
executes a zone level application and allows
communication to all LonMark devices. The
controllers are shipped with pre-loaded applications
reducing engineering start-up time.
Room Sensor Port
Room Sensor PortRoom Sensor Port
Room Sensor Port
The room sensor connection to the Controller Board
consists of a quick-connect RJ-11 jack. This
streamlines installation and reduces LTEC start-up
time.
Spare Input/Output Points
Spare Input/Output PointsSpare Input/Output Points
Spare Input/Output Points
The LTEC controller, depending upon the application
used, may have up to 3 input and 2 output spare
points available. These points can be used to perform
local connection and network control for devices
located in close proximity to the LTEC controller,
therefore reducing costs associated with installation.
Specifications
Specification
Processor Type Neuron 3150
Processor Clock Speed 10 MHz - Neuron
Network Communication TP/XF-10 (78.8K bps)
Memory Size 49 K Flash Memory
10 K SRAM
Local Network
Communication Interface
Lon port
Voltage Requirements 24 Vac @ 50/60 Hz
Power Consumption 5 VA plus loads
Ambient Operating
Environment
+32°F to +122°F
(0°C to +50°C)
5 to 95% RH (Non-condensing)
Agency Listings
UL/CUL 916 PAZX/PAZX7
(Enclosed Energy Management)
Regulatory Compliance
FCC Part 15, Class B
CISPR 22 Class B
CE Mark
C-tick
LTEC Dimensions:
8.78”H x 6.94”W x 1.85”D
(223 mm x 176 mm x 47 mm)
Weight 1.13 LBS (.51 kg)
Wiring Recommendations
Wiring RecommendationsWiring Recommendations
Wiring Recommendations
Input/AO 20 to 22 AWG
DO 18 to 22 AWG
Power 16 to 18 AWG
LonWorks Network 22 AWG Level IV per NEMA
standards
Transformer Requirements and Recommended Voltages
Transformer Requirements and Recommended Voltages Transformer Requirements and Recommended Voltages
Transformer Requirements and Recommended Voltages
Type Class 2, 24 VAC, 50/60 Hz
Ordering Information
Controllers
Description Product
Number
LTEC CH/HW FCU Controller 4IN 6DO
4 IN (2) 100 K Ω Thermistor or Dry Contact/
(2) 0-10 Vdc, 4-20 mA or Dry Contact
6 DO 24 Vac, 12VA, Triac
1 RS 10 K Ω Thermistor Room Sensor
Module
550-534
LTEC DX FCU Controller 4IN 6DO
4 IN (2) 100 K Ω Thermistor or Dry Contact/
(2) 0-10 Vdc, 4-20 mA or Dry Contact
6 DO 24 Vac, 12VA, Triac
1 RS 10 K Ω Thermistor Room Sensor
Module
550-535
LTEC CH/HW FCU Controller 5IN 8DO 2AO
5 IN (2) 100 K Ω Thermistor or Dry Contact/
(3) 0-10 Vdc, 4-20 mA or Dry Contact
8 DO 24 Vac, 12VA, Triac
2 AO 0-10 Vdc
1 RS 10 K Ω Thermistor Room Sensor
Module
550-536
LTEC DX FCU Controller 5IN 8DO 2AO
5 IN (2) 100K Ω Thermistor or Dry Contact/
(3) 0-10 Vdc, 4-20 mA or Dry Contact
8 DO 24 Vac, 12VA, Triac
2 AO 0-10 Vdc
1 RS 10 K Ω Thermistor Room Sensor
Module
550-537
Documentation
Product
Number
LTEC Owners Manual
550-311
LonWorks for APOGEE Library CD