User Manual
3/18
Building Technologies Division CC1N7495en
20.04.2016
Standards and certificates
Applied directives:
Low-voltage directive 2014/35/EC
Directive for gas-fired appliances 2009/142/EC
Electromagnetic compatibility EMC (immunity) *) 2014/30/EC
*) The compliance with EMC emission requirements must be checked after the Boiler Management Unit
is installed in equipment
Compliance with the regulations of the applied directives is verified by the adherence to
the following standards / regulations:
Automatic burner control systems for burners and applianc-
es burning gaseous or liquid fuels
DIN EN 298
Gas/air ratio controls for gas burners and gas burning
appliances
Part 2: Electronic types
DIN EN 12067-2
Safety and control devices for gas burners and gas burn-
ing appliances
DIN EN 13611
Automatic electrical controls for household and similar use
Part 2-5:
Particular requirements for automatic electrical burner con-
trol systems
DIN EN 60730-2-5
The relevant valid edition of the standards can be found in the declaration of con-
formity!
EAC Conformity mark (Eurasian Conformity mark)
ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007
Life cycle
Boiler Management Units LMU7... has a designed lifetime* of 250,000 burner startup
cycles which, under normal operating conditions in heating mode, correspond to
approx. 10 years of usage (starting from the production date given on the type field).
This lifetime is based on the endurance tests specified in standard EN 298 and the ta-
ble containing the relevant test documentation as published by the European Associa-
tion of Component Manufacturers (Afecor) (www.afecor.org
).
The designed lifetime is based on use of the BMUs according to the manufacturer’s Da-
ta Sheet and Basic Documentation. After reaching the designed lifetime in terms of the
number of burner startup cycles, or the respective time of usage, the BMU is to be re-
placed by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery