User Manual

4/9
Building Technologies Division CC1N7494en
20.04.2016
Technical data
Operating voltage AC 230 V +10 % / -15 %
Note!
Ensure that conductors L and N are correctly connected!
Mains frequency 50 Hz ±5 %
Power consumption Max. 15 VA (excl. transformer and loads)
Rated surge voltage category III ( to DIN EN 60 664)
Degree of protection IP00
IP40 (must be ensured after integration in-
to the boiler)
Safety class sections of safety class 0 and sections of
SELV
Pollution degree 2
Software classes
- Controller section
- Burner control
to DIN EN 60 730-2-5
class A
class C
Dimensions (L x H x D)
- Without housing
- With housing
180 x 180 x 45 mm
212 x 188 x 67.5 mm
Weight
- Without housing
- With housing
approx. 0.8 kg
approx. 1.15 kg
Housing (only LMU6…)
- Material
- Color
- Flame protection class
polycarbonate
RAL 7035 (light-grey)
to UL 94: V-2
Mounting position
always vertically (choice of 3 positions)
Attention!
Ensure adequate dissipation
of heat through the ventila-
tion slots!
7494u03/0102
Storage
DIN EN 60 721-3-1
Climatic conditions class 1K3
Mechanical conditions class 1M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.
Transport
DIN EN 60 068-2-30 and
DIN EN 60 730-2-5, chapter 12
Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range -20...+70 °C
Humidity < 95 % r.h.
Vibrations DIN EN 60 721-3-2
Operation
DIN EN 60 721-3-3
Climatic conditions class 3K3
Mechanical conditions class 3M2
Temperature range 0...+60 °C
Humidity < 95 % r.h.
Attention!
Condensation, formation of ice and ingress of water are not permitted!
General
Environmental conditions