User Manual
13/32
Building Technologies Division CC1N7491en
18.07.2018
Error code list
QAA73
display of
error code
Meaning of QAA73 text display
Internal
diagno
stics
code
Cause
Error 10 Error outside sensor 1 Short-circuit of outside temperature sensor
Error 20 Error boiler temperature sensor 1 1 Short-circuit of boiler temperature sensor
Error 20 Error boiler temperature sensor 1 2 Open-circuit of boiler temperature sensor
Error 28 Error flue gas temperature sensor 1 Short-circuit of NTC flue gas sensor
Error 28 Error flue gas temperature sensor 2 Open-circuit of NTC flue gas sensor
Error 50
Error DHW temperature sensor / thermostat
1
1 Short-circuit of DHW sensor
Error 50
Error DHW temperature sensor / thermostat
1
2 Open-circuit of DHW sensor
Error 61 Error room unit 1 20 No telegram received within the timeout time
Error 110 Safety limit thermostat lockout 0 Opening of high limit thermostat
Error 119 Water pressure switch has cutout 0 --
Error 125 Maximum boiler temperature exceeded 20 Pump error due to no temperature gradient
Error 125 Maximum boiler temperature exceeded 21 Pump error due to high temperature check
Error 130 Maximum flue gas temperature exceeded 0 --
Error 131 Burner lockout 0
Pump error due to temperature check or
NTC flue gas sensor
Error 133
Safety time for flame establishment
exceeded
0 --
Error 151 BMU internal error 32 Not existing Zeiko number
Error 151 BMU internal error 33-41 Time overrun in time slot detected
Error 151 BMU internal error 48 Not existing cycle number
Error 151 BMU internal error 65
Program counter was in undefined ROM
area
Error 151 BMU internal error 66 Not allowed interrupt vector
Error 151 BMU internal error 67 Stack overflow
Error 151 BMU internal error 68 Error in calculating the heating demand
Error 151 BMU internal error 82 Invalid init state
Error 152 Error parameter setting 20 Invalid parameter version number
Error 152 Error parameter setting 21 Invalid software type
Error 152 Error parameter setting 22 Invalid CRC parameter
Error 155 Remote lockout release blocked -- Not displayed on the LMU34, but on QAA73
Error 156 Error supply voltage 20
Low Voltage Fault (burner control start
prevention)
Error 156 Error supply voltage 21
Low Voltage Fault (indication, no start
prevention)
Error 156 Error supply voltage 22
Over Voltage Fault (indication, no start
prevention)
Error 158 Error condensate 0 Condensate pump continuous operation