Technical data (cont´d)
Ionization current DC switching threshold 0.45 µA (typically)
Possible ionization current Max. 11 µA
Short-circuit current Max. 51 µA
Response time in the event of loss of
flame
<1 s
Safety time «TSA» 5 s
Repetition Max. 3
Connection PELV
Type Stocko: MKS1852-6-0-202
2 poles, coded
Connections are interchangeable and
short-circuit-proof
short-circuit might lead to activation of
special LMU34… functions
Lumberg: 2.5 MSF02(3114)
2 poles
Loads Connected to LMU34… PELV
Siemens AG system-internal connection
Function Interface (OpenTherm) for QAA73…
for more detailed information, refer to
OpenTherm specification and Basic
Documentation QAA73… (P2284)
Connection HT mains voltage connection (potential-
free)
Type Molex: 1008-5031
3 poles, coded
Loads AC 230 V
2 A, cosι 0.8 Imax
fusing max. T3.15H250 to IEC 60127
Assignment Pin 1: Relay NC contact
Pin 2: Relay NO contact
Pin 3: Relay COM contact
Function Changeover contact for control of heating
circuit zone pump / alarm message
NO contact closed when there is a heat
request from QAA73… / alarm
NC contact closed when there is no heat
request from QAA73… / alarm
External system components
External system components are devices such as
Ignition equipment
Fan
Gas valve
Flow switch Hall sensor DHW
Heating circuit pump
The external system components used must be approved by Siemens AG!
Flame supervision with
ionization probe
Connector X800
Connector X301