User Manual

99
Practical tips
• Device reset by pressing and holding the
programming button (A1) for more than
20 seconds. This reverts the configuration
of the device back to the factory settings.
(Caution! If this is done, the device will
lose all assignments and physical addresses.)
• Remove unassigned or existing ECG
• Possible error with “Fb“
• After successful commissioning,
create an export (backup)
• The DALI terminals are short-circuit-proof and
resistant to external voltage during initialization
• Unfiltered line/area couplers and repeaters
can cause communication problems
Error messages
Display Description
_b Bus operation
_d Direct operation
. Device awaits ETS programming
F_ Error detected
F0 Lamp defective
F1 ECG defective
F2 Emergency light converter defective
F4 DALI device selection
F5 DALI short circuit
F6 No ECG found
88
Error (flashing). External voltage detected. External
voltage was detected at the DALI terminals A10 and A11.