User Manual

10
Replace a defective DALI ECG without ETS
Key prerequisites
• The ECG must not have a short
address (delivery state or reset)
Same device type
• The bus and main power
must be switched on at all ECGs
1
736
A1 A2
A8
A7
A6
A11A10A12A9
A5
A4
A3
Button Indicator Description
1.
Replace defective DALI-ECG with
a new ECG (delivery state)
2. A6
Call up the menu by pressing A6
3. A7
▲▼
Using the A7 button, call up
the menu option “Replace ECG”
4. A6 (short)
5. A6 (long)
(ashing)
6.
Result:
E0 = No error
E1 = Short address already assigned
E2 = Device type cannot be changed
E3 = Wrong device type
E4 = New ECG not found
E5 = Too many new ECGs found
E6 = Unknown error has occurred
7. A3
Pressing button A3 twice takes you
from the menu to the status display.